F3 Series Charger Manual
9
LED Indicators on Charger Front Panel
Indicates that AC power is being supplied to the charger.
The charger is operating in the BOOST mode.
The charger is operating in the FLOAT mode.
Indicates that AC power is not avail
able to the charger. Input AC is failed, or AC breaker is tripped.
Indicates that the charger is failing to produce the output current required by the battery and load. When
the battery and load demand no current the failure alarm will not act
ivate.
In the event that the CHARGE FAIL and AC ON lights are illuminated simultaneously, then the charger
has failed. The probable causes of an alarm, in descending order of likelihood are:
er has malfunctioned
Indicates that DC voltage has dropped to approximately 8.5% below nominal battery voltage (e.g. 22
volts for a 24 volt system). Probable causes:
a) The AC power has failed, and the battery has become discharged
er has malfunctioned and the battery has become discharged
c) The battery is defective
There is a time delay in the low voltage alarm which prevents the alarm from activating until
approximately 30 seconds after the low voltage condition starts.
Indicates that the charger’s output has exceeded a pre
-set threshold level (approximately 20% above
-
e.g. 29 volts for a 24 volt system). If this alarm stays activated for any period of
time, the charger should be shut down and
serviced. The charger may have malfunctioned, or the alarm
card may be misadjusted. The alarm actives immediately upon high voltage condition, but stays activated
for approximately 30 seconds after the condition disappears.